Intumescent Fire Dampers
Brand: Lorient

Fire Rated Air Transfer Grilles

Insulating and non-insulating Fire Rated Air Transfer Grilles system approved on various wall types.

System No.  Building Element  Product  Max Size  FRL System Detail
FR ATG Wall 1  Masonry or concrete walls LVH44 1200mm x 2400mm Up to -/240/120 Insulating LVH44 air transfer grille in
masonry or concrete walls
FR ATG Wall 2 CSR Hebel® wall LVH44 1200 x 2400mm Up to -/120/120 Insulating LVH44 air transfer grille
CSR Hebel® walls
FR ATG Wall 3 Pronto Panel LVH44 1200mm x 2400mm Up to -/120/120 Insulating LVH44 air transfer grille
Pronto Panel walls
FR ATG Wall 4  Masonry or concrete walls LVH44 1200 x 2400mm Up to -/240/- Fire rated air transfer grille in
masonry or concrete walls
FR ATG Wall 5  CSR Hebel® wall LVH44 1200 x 2400mm Up to -/120/- Fire rated air transfer grille in
CSR Hebel® walls
FR ATG Wall 6 Speedpanel® LVH44 1200 x 2400mm Up to -/120/- Fire rated air transfer grille in
Speedpanel® wall
FR ATG Wall 7  Pronto Panel LVH44 1200 x 2400mm Up to -/120/- Fire rated air transfer grille in Pronto Panel walls
FR ATG Wall 8  Masonry or concrete walls LVH44 Max aperture size:
1000mm x 500mm
Up to -/240/120
One direction only
Surface mounted over aperture
concrete or masonry wall
FR ATG Wall 9 CSR Hebel® wall LVH44 Max aperture size:
1000mm x 500mm
Up to -/120/120
One direction only
Surface mounted over aperture
CSR Hebel® wall
FR ATG Wall 10 Pronto Panel LVH44 Max aperture size:
1000mm x 500mm
Up to -/120/120
One direction only
Surface mounted over aperture in Pronto Panel wall
FR ATG Wall 11 Pronto Panel LVH44 1000mm x 500mm Up to -/120/120
One direction only
Surface mounted over aperture in Pronto Panel wall

Approval Reference: EXOVA EWFA 55205900
Relevant Standard: AS1530.4 2014