Damper installation system approved on Speedpanel wall system.
Intumescent Fire Dampers
Brand: Lorient
Speedpanels®
System No. | Building Element | Product | Max Size | FRL | System Detail | Approval Reference |
Speed panel® 1 |
51mm, 64mm, 78mm Speedpanel® wall | LVH44 | 1000mm x 1000mm | Up to -/120/- | General installation detail | EXOVA EWFA RIR 21622-31 |
Speed panel® 2 |
51mm, 64mm, 78mm Speedpanel® wall | LVH44 | 450mm x 450mm | Up to -/120/30 | In duct angles both sides | EXOVA EWFA 33233400 |
Speed panel® 3 |
51mm, 64mm, 78mm Speedpanel® wall | LVH44 | 450mm x 450mm | Up to -/120/30 | In duct angles both sides | EXOVA EWFA 33233400 |
Speed panel® 4 |
51mm, 64mm, 78mm Speedpanel® wall | LVH44C Circular | Up to 450mm diameter | Up to -/120/60 | In duct angles both sides | EXOVA EWFA 33233400 |
Speed panel® 5 |
51mm, 64mm, 78mm Speedpanel® wall | LVH44 | 450mm x 450mm | Up to -/120/30 | Mounted in wall with eggcrate cover grille | EXOVA EWFA 33233400 |
Standard Version: Speedpanels® 1-5: AS1530.4 2014